I-7011, I-7018 User ManualRev:B1.0
2.6 $AA1
Description : Perform Zero Calibration
Syntax : $AA1[CHK](cr)
$ delimiter character
AA address of setting module (00 to FF)
1 command for performing zero calibration
Response : Valid Command : !AA[CHK](cr)
Invalid Command : ?AA[CHK](cr)
Syntax error or communication error may get no re-
sponse.
! delimiter for valid command
? delimiter for invalid command or the calibration is not
enabled
AA address of response module(00 to FF)
Example :
Command : $011 Receive : !01
Perform address 01 zero calibration, return success.
Command : $021 Receive : ?02
Perform address 02 zero calibration, return the calibration is
not enabled before perform calibration command.
Related Command :
Sec.2.5 $AA0, Sec.2.20 ~AAEV
Related Topics :
Sec.1.9 Calibration